Masonpro Home
 On-Line Store
Home
On-Line Store Products Masonry Resources Information Request Contact Us About Us

Question & Answer Section
 
Topic: Rebar Lap Splicing
 
Question:
How do you calculate correct rebar lap splicing to meet code?

Answer:
The IBC 2006 adopted MSJC 2005 by reference; however they decided to keep the previous lap lengths of 48 bar diameters. ...that engineers may have the option of using MSJC 2005 for their design lap lengths. Depending on the f’m the lap lengths can be shorter particularly in the smaller bar sizes. ...Footnotes (1) & (2) represent comments in the IBC code. (1) instructs the engineer on additional lap requirements in areas of high stress, (2) addresses the requirements for epoxy coated rebar. Footnote (3) assumes the bars are spaced at least 8” on center if the bars are closer the table will need to be adjusted. All bars are centered in the wall, if the bars are designed off center the table will need to be adjusted. The f’m is a variable that may be changed to meet your project requirements. The IBC 2009 has adopted MSJC 2008 including the lap lengths. These laps match the MSJC 2005 requirements so the MSJC laps should be what we see in the future.
Below is a lap splice spreadsheet, provided by Kelly Walker of the Masonry Institute of Michigan, which has been updated for IBC 2006 as adopted in MBC 2006. Also below, are the MSJC 2005 laps.
Submitted by Kyle Lochonic
With Support From:
MIM logo
 
   
Supporting Documents:  


Required Lap Length of Bars in Inches

Click here for document


Required Lap Length of Bars in Inches  
   

8" & 12" CMU (bar in center - rebar sizes #3 - #8)

Click here for document

www.mim-online.org
8" & 12" CMU  
   

 
Topic: Locating CMU Control Joints
 
Question:
What is the approximate spacing of Control Joints (CJ’s) for reinforced CMU?

Answer:
Using the Empirical Method in NCMA TEK 10-2B, Table 1 calls for a length to height ratio of 1.5 not to exceed 25ft. This assumes you have wire every 16” o.c. The engineering method in NCMA TEK 10-3 has different ratios but still does not exceed 20 or 25 ft.

Kelly L.K. Walker
Architectural Services Director
Masonry Institute of Michigan, Inc.
MIM logo
 
Supporting Documents:   
NCMA TEK 10-2B
Control Joints For Concrete Masonry
Walls - Empirical Method


Click here for Tek Note


NCMA TEK 10-2B
   
NCMA TEK 10-3
Control Joints For Concrete Masonry
Walls- Alternative Engineered Method


Click here for Tek Note

www.ncma.org
NCMA TEK 10-3
   

 
Topic: Locating Brick Veneer Expansion Joints (EJ's)

Question:
What are the approximate spacing for Expansion Joints (EJ's) for a typical brick veneer application?

Answer:
Please read the following supporting documents.

Supporting Documents:
 

BIA Tech Note 18A
Accommodating Expansion of Brickwork

Click here for Technical Note

www.gobrick.com

TechNote 18A
   

Brick Expansion Joints and
Wall Openings
By: J Gregg Borchelt, PE
Courtesy of The Story Pole

Click here for article

Brick Expansion Joints and Wall Openings

   
Topic: CMU Wire Reinforcing Wire Reinforcing


Question:

What is the best wire for Single Wythe CMU and for Multi-Wthe CMU Cavity Wall?

Answer:
Contrary to popular belief, wire reinforcing today typically offers no structural stability. In fact, the primary purpose of wire reinforcement in modern masonry wall systems is simply to help resist CMU shrinkage cracking. Typically, vertical and bond beam rebar reinforcement serves to resist wind loading.

Truss wire is not recommended for use is reinforced CMU. Diagonal cross rods make it impossible to meet modern grouting standards referenced in the IBC and sub-referenced in ACI Building Code Requirements for Masonry Structures. Ladder wire with cross rods spaced 16 inches on center allows code required centering of rebar, freer flow of grout and promotes full embedment in mortar at every intersection where side and cross rods meet on the inner and outer CMU face-shell, resisting wall shrinkage.

Supporting Documents:
 

Climb the Ladder
To Improve Wall Reinforcing Design
Written by Kyle Lochonic & Jeff Snyder
and is published in the Masonry Magazine.

Click here for article

Climb the Ladder
Building Code Requirements and
Specification for Masonry Structures

Reported by the Masonry Standards
Joint Committee (MSJC)

Click here for Building Code Requirement

Building Code Requirement

NCMA TEK 12-1A
Anchors and Ties for Masonry


Click here for Tek Note

www.ncma.org
NCMA TEK 12-1A
   
 
Question:
Is wire reinforcement with 3/16 inch diameter side rods or 3/16 inch diameter side and cross rods better than standard 9 gauge side and cross rods?

Answer:
No, for the most part it is just the opposite. The primary purpose for wire in todays reinforced walls is to reduce CMU wall shrinkage. It is very difficult to surround 3/16 inch diameter wire with mortar when placed in 3/8 inch bed joints. This is especially evident when considering allowed tolerances for masonry units and joint sizes. Mortar better surrounds wire when utilizing 9 gauge flush welded side and cross rods, increasing resistance to shrinkage cracking. It is no surprise demand for truss wire has fallen significantly in the last decade. The market simply demands higher performance 9 gauge 16 inch core-clear ladder!

Supporting Documents:  
TECH Talk
Daniel S. Zechmeister, P.E.
Executive Director

Masonry Institute of Michigan, Inc.
MIM logo


Click here for article

www.mim-online.org

TECH TALK
Selecting the right reinforcement for the job
Mario J. Catani


Click here for article
Selecting the right join reinforcement for the job
 
MASONPRO, Inc.
 1-800-659-4731

 © 2001 - 2010 Masonpro, Inc.